How do I regenerate the desiccant in my EDH-4, RCD-1, or RCD-2 dehydrators?

Posted by on Jan 17, 2012 in Frequently Asked Questions | 0 comments

The EDH-4, RCD-1, and RCD-2 dehydrators do not have the means to automatically regenerate their drying agent. These units use a...

Read More

Can I extend the wires and how far away can I locate the sensors?

Posted by on Aug 4, 2011 in Frequently Asked Questions | 0 comments

Yes. The sensor wires can be extended up to 500 feet with #18 awg wire and 2000 feet with #12 awg wire.

Read More

Can I use a GIT-1 sensor to replace the sensor on my GIT-4 controller?

Posted by on Aug 4, 2011 in Frequently Asked Questions | 0 comments

In a word: No! The GIT-1 is meant for use with the newer APS-C series controllers, EUR-5A controller and the upcoming PRO series...

Read More

Both the heater and supply lights are flashing on the RCU-2 remote for my GIT-4, what does it mean?

Posted by on Aug 4, 2011 in Frequently Asked Questions | 0 comments

There are two possibilities and it depends on how the lights are flashing. If the lights are flashing on and off equally, that is they are...

Read More

Can I use a GIT-4 gutter deicing controller to control external contactors?

Posted by on Aug 4, 2011 in Frequently Asked Questions | 0 comments

No, using an external contactor will cause the GIT-4 to indicate a ground fault and keep it from functioning.

Read More

Can I use the GIT-3A controller to power heat cables directly?

Posted by on Aug 4, 2011 in Frequently Asked Questions | 0 comments

Yes, as long as the total load does not exceed the maximum current rating of the internal relay contacts, which is 26 amps...

Read More