Can I use the GIT-3A controller to power heat cables directly?
Yes, as long as the total load does not exceed the maximum current rating of the internal relay contacts, which is 26 amps...
Read MoreHow can I test the snow sensor attached to my GIT-4 or GIT-3A gutter deice controller?
The sensors require a temperature below 38F and moisture on the moisture grid. The GIT-4 has a protruding tube that contains the...
Read MoreCan I use a GIT-1 sensor to replace the sensor on my GIT-3A controller?
In a word: No! The GIT-1 is meant for use with APS control panels, EUR-5A controls and the PRO series controls. The GIT-3A sensor is...
Read MoreDo I need to supply the controller with a ground fault breaker?
When using a control or controller that does not include integral ground fault, using a ground fault breaker is required to provide...
Read MoreWhat voltage measurement will help determine if the GIT-3A is working properly?
Aside from checking the input voltage from the circuit breaker you can also check the voltage between the red and black sensor wires. The...